<Toc> <2. Initial Settings>
IM 05D01D12-41E 6th Edition: Mar. 25, 2005-00
Note 1: The fault diagnosis output turns on in case of input burnout, A/D converter failure, or reference junction compensation
(RJC) failure.
The control output in case of input burnout or A/D converter failure is set to the value of the PO (Preset Output Value)
setup parameter. In case of RJC failure, the controller continues control under the condition of RJC = OFF.
Note 2: The FAIL output is on during normal operation and turns off in case of failure.
Note 3: The difference of alarm action between the alam type codes 3 to 8, 13 to 18 and 33 to 38, 43 to 48 in the table above
is as follows.
The codes 3 to 8, 13 to 18 are effective for current setpoints. (For example, they are effective for the ramp rate setpoint
at SP switching.)
The codes 33 to 38, 43 to 48 are effective for target setpoints. (For example, they are not effective for the ramp rate
setpoint at SP switching.)
Treated
as normal
C
Power-on
Time
The alarm output does not
turn on in this region even
if the PV value is below the
low limit of the alarm setpoint.
Low limit of
alarm setpoint
Normal Abnormal
The alarm
output turns on.
Stand-by Action
It is effective in the following cases where;
- the power is turned on
- the target setpoint is changed
- the target setpoint number is switched
(however, except for remote setpoint)
- the alarm type is changed