All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar. 01, 2005-00
Conformance to Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE), approved by
C22.2 No.61010-1, approved by UL508.
Installation category : CAT. II Pollution
degree: 2 (IEC/EN61010-1, C22.2 No.61010-1)
Measurement category : I (CAT. I : IEC/
EN61010-1)
Rated measurement input voltage : 10V DC
max.(across terminals), 300V AC max.(across
ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safety standard
which is assumed by IEC/EN61010-1 in
Measurement category I, and is not the value
which guarantees an apparatus performance.
EMC standards: Complies with EN61326, EN61000-3-2,
EN61000-3-3 and EN55011 (CE).
AS/NZS 2064 compliant (C-Tick).
Class A Group 1.
During test, the controller continues to operate
with the measurement accuracy within ±20%
of the range.
Construction, Mounting, and Wiring
Construction: Dust-proof and Drip-proof front panel
conforming to IP55.
For side-by-side close installation, the
controller loses its dust-proof and drip-proof
protection.
Material: ABS resin and polycarbonate
Case color: Black
Weight: About 1 kg or less
External dimensions:
48 (W) × 96 (H) × 100 (depth from the panel
face) (mm)
Mounting: Direct panel mounting; mounting bracket, one
each for upper and lower mounting
Panel cutout dimensions:
45
+0.6
0
(width) ×
92
+0.8
0
(height) mm
Mounting attitude:
Up to 30 degrees above the horizontal. No
downward tilting allowed.
Wiring: M3.5 (ISO 3.5 mm) screw terminals (signal
wiring and power/ground wiring as well)
Power Supply and Isolation Specifications
Power Supply Specifications
Power supply: Voltage rating at 100 to 240 V AC (±10%),
50/60 Hz
Power consumption: Max. 20 VA (Max. 8.0 W)
Internal fuse rating: 250 V AC, 1.6 A time-lug fuse
Memory back-up: Non-volatile memory (service life about
100,000 times of writings)
Withstanding voltage:
1500 V AC for 1 minute between primary and
secondary terminals
1500 V AC for 1 minute between primary and
ground terminals
1500 V AC for 1 minute between ground and
secondary terminals.
500V AC for 1minute between two secondary
terminals
Primary terminals: Power supply and relay output
terminals
Secondary terminals: Analog input/output signal
terminals, voltage pulse output terminals,
and contact input terminals
Isolation resistance:
Between power supply and grounding
terminals, 500 V DC 20 M or more
Grounding: Class D gronding (Class 3 grounding)
(grounding resistance of 100 or less)
Isolation Specifications
PV input terminal:
Isolated from other input/output terminals.
Not isolated from internal circuits.
15 V DC loop power supply terminal:
Not isolated from 4-20mA analog output
and voltage pulse control output. Isolated
from other input/output terminals and
internal circuit.
24 V DC loop power supply terminal:
Isolated from other input/output terminals
and internal circuit.
Control output (current or voltage pulse) and retransmis-
sion terminal:
Not isolated between control output and
retransmission output terminals. Isolated
from other input/output terminals and
internal circuits.
Relay contact control output terminal:
Isolated from other input/output terminals
and internal circuits.
Contact input terminal:
Not isolated from other contact input
terminals mutually, and from communica-
tion terminals. Isolated from other input/
output terminals and internal circuits.
Relay contact alarm output terminal:
Isolated from other input/output terminals
and internal circuits.
RS-485 communication terminal:
Not isolated from contact input terminals.
Isolated from other input/output terminals
and internal circuits.
Power supply terminal:
Isolated from other input/output terminals,
grounding terminal, and internal circuits.
Grounding terminal:
Isolated from other input/output terminals,
power supply terminals, and internal
circuits.
Environmental Conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C (40°C or less when
mounted side by side)
The operating ambient temperature range is
between 0°C and 40°C when the 24 V DC
loop power supply.
Ambient temperature change limit: 10°C/h or less
Ambient humidity: 20 to 90% RH (no condensation)
Magnetic field: 400 A/m or less
Continuous vibration (5 to 14 Hz):
Peak-to-peak amplitude of 1.2 mm or less
Continuous vibration (14 to 150 Hz):
4.9 m/s
2
or less
Short-period vibration: 14.7 m/s
2
or less, 15 s
Shock: 147 m/s
2
or less, 11 ms
Installation altitude: 2,000 m or less above sea level
Warm-up time: 30 minutes or more after power on
Transportation and storage conditions:
Temperature: 25 to 70°C
Temperature change limit: 20°C/h or less
Humidity: 5 to 95% RH (no condensation)
Effects of operating conditions
Effect of ambient temperature:
For voltage or TC input:
Equal to or less than whichever is greater,
±1 µV/°C or ±0.01% of F.S./°C.
For RTD inputs:
±0.05°C/°C (ambient temperature) or less
For analog output:
±0.05% of F.S./°C or less
Effect of power supply fluctuation (within rated voltage):
For analog input:
Equal to or less than whichever is greater,
± 1 µV/10 V or ± 0.01% of F.S./10 V.
For analog output:
±0.05% of F.S./10 V or less